( 1 ) Determination of capacity: According to the long-term continuous operation of the unit, the output power can meet the maximum calculation load selection of the whole project , and the reserve unit capacity of the generator unit should be determined according to the importance of the load. The continuous output power of the diesel engine is generally 0.9 times the calibrated power . ( 2 ) Determination of the number of units: The general setting is usually more than 2 units to ensure the continuity of power supply and adapt to changes in the power load curve. Only when the number of units is large can the number of units to be put into the generator set be determined according to the changes in the electrical load, so that the diesel engine is often operated under economic load to reduce the fuel consumption rate and reduce the cost of power generation. The best economical operating state of the diesel engine is between 75%-90% of the rated power . In order to ensure the continuity of power supply, the common units themselves should consider setting up standby units. ( 3 ) Determination of speed . ( 4 ) Determination of voltage: The determination of generator output voltage is the same as that of emergency generator sets, generally 400V , and high-voltage generator sets can be used for projects with large power consumption and long transmission distances .